A client reported deficiencies in operation of FC 225 IOC/DOUT Digital Out/Channel blocks in a FC 228 FDD chain when S5 was left at the default value 0. The documentation clearly states for S5:

"(Readback enable) The output channels can have optional readback hardware present. This specification must match the hardware configuration with respect to whether this option is enabled.

. 0 = disable readback

. 1 = enable readback

This option must always be enabled for foreign device definition (function code 228) channels."

The client reported"The logical input will not match the output of the function code at times, even though the physical output will. Also, it was noticed that even overriding the output will not update this. The exception reporting is the output of the block. So in our case, we have these trended in PI and have graphics showing the state of these blocks. All of these, were reporting the wrong state when there were changes to the input. This leads to misconceptions when troubleshooting. Also, problems with reporting if external logic is using these exception reports (PI calculations, graphical procedures, etc.).

We typically don’t use the output exceptions for alarming. But did notice a few, while monitoring in composer, (that were setup to alarm) to have similar symptoms. So, I would assume the alarm state to be dictated by the output state and not the input. Given that, I would also assume that if there was logic built based on the output of the block, it would not function correctly. I don’t think we are doing this anywhere, but others may."


The client then changed S5 to 1 for the blocks. Here is an additional statement:


"Some did change state or got exception reported as expected. Also, the problem seemed to have cleared when an online configuration was made to something unrelated but in the same module, only to show up again on different blocks within a day or so. The problem seemed to be with the block output more than the exception reporting. Monitoring the block outputs of the suspect blocks from Composer or DBDOC did not match what it should’ve been. Don’t know the internals on how the exception reporting is done, but, it sure seems like if the output doesn’t change state (when it is supposed to), exception reporting does not function as well. Could not see any correlation of the errors, seemed random. Now, after the spec change, we don’t see any mismatches, so far (~3weeks)."


Bottom line is that the output of the block does not match the input, affecting tags, history, exception report inputs as well as local use of the block.


This seems inconceivable. What am I missing? Can someone explain what happens in FDD chains to FC225 output values if S5=0, as it clearly must be 1? What goes wrong from your knowledge? In a scan of half a dozen systems, I found only one that used the correct value - that is, about 10,000 errors in five systems.



Add New Comment


Geoff Michaels   

asked 3 months ago
Closed



Best Answer

1

FC225 NOT UPDATING THE "OUTPUT INDICATION" HAS BEEN A PROBLEM FOR A WHILE.

IN ALL MY EXPERIENCES THE PHYSICAL OUTPUT IS ACTUALLY STILL WORKING.

POWERING DOWN THE AFFECTED I/O AND RE-POWERING ALSO RESETS INDICATIONS.

THE MOST RECENT SOLUTION TO THE PROBLEM WAS TO INSTALL BRC 400/410 REV M5 FIRMWARE AND S800/810 FIRMWARE TO G5.

I HAVE DONE THIS AND HAVE NOT SEEN THE PROBLEM SINCE.

I HAVE NOT HAD TO UPDATE S5 AS INDICATED TO SOLVE THE ISSUE, BUT THIS SEEMS LIKE A PRUDENT THING TO DO, EITHER WAY.

ALSO SEE CASE

ABB20161007E0252

Mayers.KE   

answered 3 months ago


 


By Geoff Michaels on 8/16/2017 | Like (0) | Report

Thanks. This explains why the problem has not been prevalent. You have given the ABB case that documents the problem and its resolution.

To summarize:

1. If your firmware is upgraded, you likely can ignore S5 and the indication should always be correct.
2. In any event, without upgraded firmware, the problem is that tags and alarms on the FC225 blocks can fail to work, along with LOGIC WIRED TO THE OUTPUT. This is highlighted because it shows a process vulnerability.

We now flag this situation. DBDOC Error Browser allows trivial "hiding" of messages if your firmware is up to date, if there is no tag, or there is no use made of the output block. What is left would be worth addressing.

Bottom line: There are some sites out there with unpredictable values in subsequent logic, alarms and displayed values. Many will have the problem resolved without ever knowing it existed.


Add New Comment


Answers

1

FC225 NOT UPDATING THE "OUTPUT INDICATION" HAS BEEN A PROBLEM FOR A WHILE.

IN ALL MY EXPERIENCES THE PHYSICAL OUTPUT IS ACTUALLY STILL WORKING.

POWERING DOWN THE AFFECTED I/O AND RE-POWERING ALSO RESETS INDICATIONS.

THE MOST RECENT SOLUTION TO THE PROBLEM WAS TO INSTALL BRC 400/410 REV M5 FIRMWARE AND S800/810 FIRMWARE TO G5.

I HAVE DONE THIS AND HAVE NOT SEEN THE PROBLEM SINCE.

I HAVE NOT HAD TO UPDATE S5 AS INDICATED TO SOLVE THE ISSUE, BUT THIS SEEMS LIKE A PRUDENT THING TO DO, EITHER WAY.

ALSO SEE CASE

ABB20161007E0252

Mayers.KE   

answered 3 months ago


 


By Geoff Michaels on 8/16/2017 | Like (0) | Report

Thanks. This explains why the problem has not been prevalent. You have given the ABB case that documents the problem and its resolution.

To summarize:

1. If your firmware is upgraded, you likely can ignore S5 and the indication should always be correct.
2. In any event, without upgraded firmware, the problem is that tags and alarms on the FC225 blocks can fail to work, along with LOGIC WIRED TO THE OUTPUT. This is highlighted because it shows a process vulnerability.

We now flag this situation. DBDOC Error Browser allows trivial "hiding" of messages if your firmware is up to date, if there is no tag, or there is no use made of the output block. What is left would be worth addressing.

Bottom line: There are some sites out there with unpredictable values in subsequent logic, alarms and displayed values. Many will have the problem resolved without ever knowing it existed.


Add New Comment



Get weekly AKS updates


Partner Exclusive Webinars

 

> – Login to the partner portal to register



Points Redemption Program - Redeem your points for ABB training, Bluetooth speakers and mugs. Terms and conditions >


Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more



AKS Experts


avatar
Ask Rob Lyon   

Rank: 3

info@lymac.co.nz I'm an independent DCS software and commissioning engineer with extensive experience in 800xA and other ABB products. I've worked in almost every corner of the world and still haven't seen it all.


avatar
Ask MMM   

Rank: 5

ABB PA CT Technical Support


avatar
Ask nikismith   

Rank: 266

I have been a part of the Recording & Control Factory team for 17 years in total, having spent a number of years as a repairs technician withi the manufacturing department, but being in my current role for 9 years now.


avatar
Ask kstoilov   

Rank: 15

Control System Engineer: 800xA, Compact 800, AC500, AC31-50, Advant Master, Simatic, AC&DC Drives 11 years worked for ABB - Control Systems


avatar
Ask Govindaraj   

Rank: 10

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.


avatar
Ask Flavio Mussolin   

Rank: 4

ABB AVP, Senior Electronic and Automation Engineer with over 30 years of experience in the field of process automation automotive, pharmaceutical, hollow glass, steel and rolling.


avatar
Ask Harsha.D   

Rank: 6

Tech.Support,software and commisioning engineer with Proficient knowledge in 800xA and its products, RNRP,Networking in general.


avatar
Ask Dieter Henkel   

Rank: 23


avatar
Ask Stefan Stromqvist   

Rank: 1

I joined ABB in the year of 1994 and has since 1999 been working as a Service & Support Engineer at BU Control Technologies in Västerås, Sweden. My areas of expertise are: 800xA Base, 800xA for Advant Master, Information Management, operating systems, RNRP and Ethernet comms/networking in general.


avatar
Ask Sumit Gargav   

Rank: 2

I have worked with Freelance in majority, with 800xA FD and Melody system partly. Also had opportunity to work with Protocols - HART,Profibus,FF & Modbus.