How to configure Soft Controller in Compact control builder AC 800M(Ver 5.1) for testing program.


Add New Comment


maanuaanu   

asked 1 year ago
Closed



Best Answer

6

For "testing" program you do not need SoftController. There are dedicated "Test Mode" function available.

If you wish to simulate control application (Online mode) then the SoftController can be used.

Configuration is simple:

1. Launch SoftController application from Windows start menu and click "Start".

2. In Compact Control Builder menu select "Tools->Setup->Station->Application Download". Change HWSimulationAllowed parameter to "TRUE". Change ReauthenticateDL to "FALSE".

3. Expand "Controllers" tree in Control Builder, right-click controller you want to simulate and select "Properties->Simulate Hardware".

4. Right-click same controller again and select "Properties->System Identity". Here you must set address of SoftController. If SoftController is running on the same computer with Control builder set the address: 127.0.0.1:2. Else, open SoftController application click File->View Log and check which network address has been assigned.

5. Expand "Hardware AC800M" of your controller, find ethernet settings and change IP address to 127.0.0.1 or on the IP that has been assigned to SoftController (see SC log file) but without postfix ":2".

6. Click "Download Project and Go Online" button (or press Ctrl+D) in the Control Builder.

All done.

Source: 

Linkinx64   

answered 1 year ago


 


By maanuaanu on 2/1/2013 | Like (0) | Report

Thank You for a quick reply


By vnnghia_bk on 4/29/2013 | Like (0) | Report

Can I and how can simulate 2 or more than 2 plc AC800M at the same time with soft controller?


By admin on 4/30/2013 | Like (0) | Report

Hello vnnghia_bk,
Recommended to ask question as new thread to get more response. Good luck!


By Linkinx64 on 4/30/2013 | Like (0) | Report

Yes, you can. But more than 2 softcontrollers is not officiall feature of 800xA and AC 800M. There will be some limitation in simulation mode such as MMS connectivity problem.


Add New Comment


Answers

6

For "testing" program you do not need SoftController. There are dedicated "Test Mode" function available.

If you wish to simulate control application (Online mode) then the SoftController can be used.

Configuration is simple:

1. Launch SoftController application from Windows start menu and click "Start".

2. In Compact Control Builder menu select "Tools->Setup->Station->Application Download". Change HWSimulationAllowed parameter to "TRUE". Change ReauthenticateDL to "FALSE".

3. Expand "Controllers" tree in Control Builder, right-click controller you want to simulate and select "Properties->Simulate Hardware".

4. Right-click same controller again and select "Properties->System Identity". Here you must set address of SoftController. If SoftController is running on the same computer with Control builder set the address: 127.0.0.1:2. Else, open SoftController application click File->View Log and check which network address has been assigned.

5. Expand "Hardware AC800M" of your controller, find ethernet settings and change IP address to 127.0.0.1 or on the IP that has been assigned to SoftController (see SC log file) but without postfix ":2".

6. Click "Download Project and Go Online" button (or press Ctrl+D) in the Control Builder.

All done.

Source: 

Linkinx64   

answered 1 year ago


 


By maanuaanu on 2/1/2013 | Like (0) | Report

Thank You for a quick reply


By vnnghia_bk on 4/29/2013 | Like (0) | Report

Can I and how can simulate 2 or more than 2 plc AC800M at the same time with soft controller?


By admin on 4/30/2013 | Like (0) | Report

Hello vnnghia_bk,
Recommended to ask question as new thread to get more response. Good luck!


By Linkinx64 on 4/30/2013 | Like (0) | Report

Yes, you can. But more than 2 softcontrollers is not officiall feature of 800xA and AC 800M. There will be some limitation in simulation mode such as MMS connectivity problem.


Add New Comment


1

Hello,

Find detail information in getting started document @ http://search.abb.com/library/Download.aspx?DocumentID=3BSE041584-510&LanguageCo
de=en&DocumentPartId=&Action=Launch
, page 29

Hope that will help you...

Sumit Gargav   

answered 1 year ago


 


By maanuaanu on 2/1/2013 | Like (0) | Report

yup, it helped


Add New Comment



Get weekly AKS updates

Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more 


Winners revealed for Bose Bluetooth speaker. Check if you are a winner



Bose speaker image


AKS Experts


avatar
Ask Stefan Stromqvist   

Rank: 2

I joined ABB in 1994 and has since 1999 been working as a support engineer at Process Automation in Västerås, Sweden. My areas of expertise are 800xA Base, 800xA for Advant Master, Information Management, legacy Advant/Master, RNRP and computer operating systems and networking in general.


avatar
Ask Prashanth   

Rank: 6

Marine Library Development, IDC, Bangalore


avatar
Ask Burkhard   

Rank: 23

Burkhard provides technical SALES support focused on Freelance in Central Europe. He joined ABB in 2007. Burkhard holds a Master of Science degree in Industrial Engineering.


avatar
Ask Govindaraj   

Rank: 10

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.