I have redundant CI 868 to get data from ABB protection relays REF630 and RET630 relays. I am facing two type of issues

CASE-1. Some groups in IED have warning because some tags in a channel are not communicating.

CASE-2. All groups in an IED have fault because all tags in all channels are not communicating.

Pictures attached for more information. Please advise way forward.

BR,

Rizwan

 CASE11.png

 CASE12.png

 CASE13.png

 CASE21.png

 CASE22.png

 CASE23.png

 CASE24.png


Add New Comment


Engr. Rizwan Hassan   

asked 10 days ago
Closed



Best Answer

1

Hello,

1.can you please check whether q parameter is configured for all Signals which causes error or warnings.. q is a mandatory parammeter for all signals.

2. if q is present in the signal check with wireshark whether signals coming from IED to CI868.

Regards,

Chanth

inchgow1   

answered 9 days ago


 


By Engr. Rizwan Hassan on 5/14/2018 | Like (0) | Report

Chanth, I investigated a bit more and found that all IED has there tag number as there technical key but the ones that are not communicating have completely different technical key than their tag number. Could this be a possible reason?


Add New Comment


Answers

1

Hello,

1.can you please check whether q parameter is configured for all Signals which causes error or warnings.. q is a mandatory parammeter for all signals.

2. if q is present in the signal check with wireshark whether signals coming from IED to CI868.

Regards,

Chanth

inchgow1   

answered 9 days ago


 


By Engr. Rizwan Hassan on 5/14/2018 | Like (0) | Report

Chanth, I investigated a bit more and found that all IED has there tag number as there technical key but the ones that are not communicating have completely different technical key than their tag number. Could this be a possible reason?


Add New Comment


1

CASE-1. Some groups in IED have warning because some tags in a channel are not communicating.

- MV.GGIO.1 to 4 and MMXU.A (Current) signals are in different dataset and GCB. If yes, Check the content of dataset and GCB parameters especially like APP ID, Mac ID, Conf Rev.


CASE-2. All groups in an IED have fault because all tags in all channels are not communicating.

- Check the content of dataset and GCB parameters especially like APP ID, Mac ID, Conf Rev.


Pls cross check the above details in the retrieved SCD file from CI868 card and CID file from IED.

ParthibanT   

answered 9 days ago


 


By Engr. Rizwan Hassan on 5/14/2018 | Like (0) | Report

I have same understanding about case 1.
Case 2, I investigated a bit more and found that all IED has there tag number as there technical key but the ones that are not communicating have completely different technical key than their tag number. Could this be a possible reason? How to retrieve CID file I only have PCM600, don't have IET software.


By Engr. Rizwan Hassan on 5/14/2018 | Like (0) | Report

Can you please further tell how can I change technical key? Will it affect operation of relay? Will it have any affect on GOOSE network?


Add New Comment



Get weekly AKS updates


Partner Exclusive Webinars

 

> – Login to the partner portal to register



Points Redemption Program - Redeem your points for ABB training, Bluetooth speakers and mugs. Terms and conditions >


Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more



AKS Experts


avatar
Ask Govindaraj   

Rank: 10

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.


avatar
Ask Harsha.D   

Rank: 7

Tech.Support,software and commisioning engineer with Proficient knowledge in 800xA and its products, RNRP,Networking in general.


avatar
Ask Dieter Henkel   

Rank: 19


avatar
Ask Flavio Mussolin   

Rank: 4

ABB AVP, Senior Electronic and Automation Engineer with over 30 years of experience in the field of process automation automotive, pharmaceutical, hollow glass, steel and rolling.


avatar
Ask Sumit Gargav   

Rank: 3

I have worked with Freelance in majority, with 800xA FD and Melody system partly. Also had opportunity to work with Protocols - HART,Profibus,FF & Modbus.


avatar
Ask Ronny Lindström   

Rank: 17

ABB Service Engineer


avatar
Ask Rob Lyon   

Rank: 2

info@lymac.co.nz I'm an independent DCS software and commissioning engineer with extensive experience in 800xA and other ABB products. I've worked in almost every corner of the world and still haven't seen it all.


avatar
Ask nikismith   

Rank: 257

I have been a part of the Recording & Control Factory team for 17 years in total, having spent a number of years as a repairs technician withi the manufacturing department, but being in my current role for 9 years now.


avatar
Ask Stefan Stromqvist   

Rank: 1

I joined ABB in the year of 1994 and has since 1999 been working as a Service & Support Engineer at BU Control Technologies in Västerås, Sweden. My areas of expertise are: 800xA Base, 800xA for Advant Master, Information Management, operating systems, RNRP and Ethernet comms/networking in general.


avatar
Ask WvanWees   

Rank: 6

I'm a senior service engineer working for ABB in The Netherlands.


avatar
Ask MMM   

Rank: 5

ABB PA CT Technical Support


avatar
Ask kstoilov   

Rank: 9

Control System Engineer: 800xA, Compact 800, AC500, AC31-50, Advant Master, Simatic, AC&DC Drives 11 years worked for ABB - Control Systems