Bumpless Transfer in PID block

Dear friends,

Any body have a experience in Bumpless Transfer for PID block?

kindly share your idea here .


Add New Comment


vigneshwaran92rce   

asked 16 days ago



Answers

0

I'm not quite sure if you mean that, but for bumpless transfer for PID block I'm using TRACK and TRACKVALUE inputs of the block.

When the PID is not active, you should activate TRACK and write Pv value to TRACKVALUE input of the PID block.

Answer belongs to AC800M blocks

For AC500, may be you should assign Actual value to Set_Point, in case you are in Manual mode

From the help:

In normal operation (MANUAL = RESET = LIMITS_ACTIVE = FALSE) the controller calculates the controller error e as difference from SET_POINT – ACTUAL, generates the derivation with respect to time de/dt and stores these values internally.

kstoilov   

answered 16 days ago


 


By vigneshwaran92rce on 6/8/2017 | Like (0) | Report

How to make it AC500 PLC?


By kstoilov on 6/8/2017 | Like (0) | Report

Look in revised answer above


By vigneshwaran92rce on 6/8/2017 | Like (0) | Report

That may be a wrong method because In manual mode operator directly controls the PID op so assigning of Actual value to Set_Point will not work


By kstoilov on 6/8/2017 | Like (0) | Report

It depends what bumpless transfer you need.
In case it is in manual mode, and Setpoint=Actual Value, after back to auto mode, the error will be 0, nothing will happen, until next vallue for the Setpoint is entered from HMI.
In auto mode, it should be in opposite - man output = PID output.


Add New Comment



Get weekly AKS updates


Partner Exclusive Webinars

 

> – Login to the partner portal to register



Points Redemption Program - Redeem your points for ABB training, Bluetooth speakers and mugs. Terms and conditions >


Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more



AKS Experts


avatar
Ask HenkelD   

Rank: 24


avatar
Ask Govindaraj   

Rank: 10

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.


avatar
Ask kstoilov   

Rank: 23

Control System Engineer: 800xA, Compact 800, AC500, AC31-50, Advant Master, Simatic, AC&DC Drives 11 years worked for ABB - Control Systems


avatar
Ask Flavio Mussolin   

Rank: 7

ABB AVP, Senior Electronic and Automation Engineer with over 30 years of experience in the field of process automation automotive, pharmaceutical, hollow glass, steel and rolling.


avatar
Ask Harsha.D   

Rank: 6

Tech.Support,software and commisioning engineer with Proficient knowledge in 800xA and its products, RNRP,Networking in general.


avatar
Ask Stefan Stromqvist   

Rank: 1

I joined ABB in the year of 1994 and has since 1999 been working as a Service & Support Engineer at BU Control Technologies in Västerås, Sweden. My areas of expertise are: 800xA Base, 800xA for Advant Master, Information Management, operating systems, RNRP and Ethernet comms/networking in general.


avatar
Ask Sumit Gargav   

Rank: 2

I have worked with Freelance in majority, with 800xA FD and Melody system partly. Also had opportunity to work with Protocols - HART,Profibus,FF & Modbus.


avatar
Ask nikismith   

Rank: 252

I have been a part of the Recording & Control Factory team for 17 years in total, having spent a number of years as a repairs technician withi the manufacturing department, but being in my current role for 9 years now.


avatar
Ask MMM   

Rank: 4

ABB PA CT Technical Support


avatar
Ask Rob Lyon   

Rank: 3

info@lymac.co.nz I'm an independent DCS software and commissioning engineer with extensive experience in 800xA and other ABB products. I've worked in almost every corner of the world and still haven't seen it all.