Hi all,

I have redundant ac800f with pc a and pc b and I want to make a change on a logic to add a set/reset block.

My question is if I dowload a new program the cpu will stop to run ot not (online change)?

Also I have to dowload from pc a or pc b or both?

What is step by step procedure?

I know very good ac800m but not ac800f.

Thank's to all

Dino


Add New Comment


dinoo31   

asked 1 month ago
Closed



Answers

2

Hello,

A) Will the controller stop?

That depends. If you just add new functions or function blocks and connect only to variables already in the process image of the task the controller will not stop. If you create new variables and connect them to your logic or if you connect to variables already known in the system, but not used in the process image of the task the controller will halt execution momentarily (while installing the change) before continuing.

If you use incremental load regularily in small steps you will hardly notice the freezing because it is usually done within one task cycle of the usual 300 ms task cycle in process automation.

B) Will I have to download from PC A, PC B or both?

You need to do the download only from the PC that hosts the Freelance Engineering (former Control Builder F). But you might need to download your changes also to each PC running a Freelance Operations [FO] software (former DigiVis). Consider adding a fucntion block, then FO needs to know about the new faceplate.

The sequence of download should always be controller, gateway / server (if any) and finally FO.

Dieter Henkel   

answered 1 month ago


 


By dinoo31 on 3/20/2018 | Like (0) | Report

Thank's for reply.
I want to add a set/rest block to sfc program to get a new condition. That's all
Shoul I load a whole station or only load changed?


By Dieter Henkel on 3/21/2018 | Like (0) | Report

Always use Load Changed Objects. The tool will tell you when a Load Whole Station is necessary.


By dinoo31 on 3/21/2018 | Like (0) | Report

Ok. So load changes will not stop a process.
Thank you very much


By Dieter Henkel on 3/22/2018 | Like (0) | Report

That's not what I said. You asked about the choice between Load whole station and Load Changed objects, which is a choice you make. Load Whole Station will stop the process and reboot the controller. That takes quite some timeand the controller restarts with initial values. Load changed objects might stops the controller for a short time as outlined in my first answer to you. But it is a short time only, freezes the outputs during the controller stop and automatically contimues with the retained values.


By dinoo31 on 3/22/2018 | Like (0) | Report

That's what I understood is when I use load changes there is no need to stop my process, of course the values will freeze for moment. On AC800M warm download (online changes) with freeze values for a moment and cold download (stop cpu).


By Dieter Henkel on 3/22/2018 | Like (0) | Report

In Freelance even with a Load Changed Object the controller might shortly stop execution of application tasks shortly while freezing the outputs. You can actually see the behaviour by looking at the colors of P-Tree nodes. Have a look at the documentaion.


Add New Comment



Get weekly AKS updates


Partner Exclusive Webinars

 

> – Login to the partner portal to register



Points Redemption Program - Redeem your points for ABB training, Bluetooth speakers and mugs. Terms and conditions >


Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more



AKS Experts


avatar
Ask Dieter Henkel   

Rank: 19


avatar
Ask Govindaraj   

Rank: 9

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.


avatar
Ask nikismith   

Rank: 255

I have been a part of the Recording & Control Factory team for 17 years in total, having spent a number of years as a repairs technician withi the manufacturing department, but being in my current role for 9 years now.


avatar
Ask Harsha.D   

Rank: 7

Tech.Support,software and commisioning engineer with Proficient knowledge in 800xA and its products, RNRP,Networking in general.


avatar
Ask Flavio Mussolin   

Rank: 4

ABB AVP, Senior Electronic and Automation Engineer with over 30 years of experience in the field of process automation automotive, pharmaceutical, hollow glass, steel and rolling.


avatar
Ask MMM   

Rank: 5

ABB PA CT Technical Support


avatar
Ask Stefan Stromqvist   

Rank: 1

I joined ABB in the year of 1994 and has since 1999 been working as a Service & Support Engineer at BU Control Technologies in Västerås, Sweden. My areas of expertise are: 800xA Base, 800xA for Advant Master, Information Management, operating systems, RNRP and Ethernet comms/networking in general.


avatar
Ask Rob Lyon   

Rank: 2

info@lymac.co.nz I'm an independent DCS software and commissioning engineer with extensive experience in 800xA and other ABB products. I've worked in almost every corner of the world and still haven't seen it all.


avatar
Ask Ronny Lindström   

Rank: 16

ABB Service Engineer


avatar
Ask WvanWees   

Rank: 6

I'm a senior service engineer working for ABB in The Netherlands.


avatar
Ask kstoilov   

Rank: 11

Control System Engineer: 800xA, Compact 800, AC500, AC31-50, Advant Master, Simatic, AC&DC Drives 11 years worked for ABB - Control Systems


avatar
Ask Sumit Gargav   

Rank: 3

I have worked with Freelance in majority, with 800xA FD and Melody system partly. Also had opportunity to work with Protocols - HART,Profibus,FF & Modbus.