Dear Gentlemen,




We recently installed new drives (ACS880) in our Hot strip mill. the controller of the drive is AC800M. The master controller is AC450. Our issue here that all drives trips without material in the mill and is giving this alarm AFE2 Emergency stop (off1 or off3).




Action taken: to reset this alarm from the MMI whenever it come.



I have consulted the vendor and they say there is an issue with the communication.




Can you please advice or suggest any possible solution.



Regards,


Associated Apps

Hands on Manual for Profinet Communication with AC800M (1.0)  Download

Freelance Modbus TCP function block for ACS880 Drive (1.0)  Download

Advant Controller 450 (AC450) automated conversion (1.0)  Download


Add New Comment


qahtaniabasa   

asked 17 days ago
Closed



Best Answer

1

It is not clear from your description how the drives are configured.

AFE2 alarms means that the drive receives Emergency stop command, it is not generated from the drive itself. From the manual:


The emergency stop signal is connected to the input selected by parameter 21.05 Emergency stop source. The mode of the emergency stop is selected by parameter 21.04 Emergency stop mode. An emergency stop can also be generated through a fieldbus (parameter 06.01 Main control word, bits 0…2)

Check how the emergency stop command is configured for your drives - parameter 21.05.

In case it is trough fieldbus, check bits 0 to 2 from main control word

kstoilov   

answered 17 days ago


 


Add New Comment


Answers

1

It is not clear from your description how the drives are configured.

AFE2 alarms means that the drive receives Emergency stop command, it is not generated from the drive itself. From the manual:


The emergency stop signal is connected to the input selected by parameter 21.05 Emergency stop source. The mode of the emergency stop is selected by parameter 21.04 Emergency stop mode. An emergency stop can also be generated through a fieldbus (parameter 06.01 Main control word, bits 0…2)

Check how the emergency stop command is configured for your drives - parameter 21.05.

In case it is trough fieldbus, check bits 0 to 2 from main control word

kstoilov   

answered 17 days ago


 


Add New Comment


1

My guess is ... If its a hot strip mill its typically a sectional drive application, where the AC800M is responsible for coordinating the setpoints between all the drive sections and handling all of the operator interface, diagnostics, interlocking etc. The AC450 probably isn't involved much at all (if any)

My very strong advice is, you can of course look at the drive settings but DO NOT CHANGE THE ACS800 DRIVE PARAMETERS. These drives are configured to be controlled pretty much entirely by the AC800M.

"Off1" and "Off3" are bits 1 and 3 of the control word and should be held "ON" for the drive to run (as well as "Off2"). A comms failure between the AC800M and the drive would likely see these bits "lost" or set to zero.

Without a detailed understanding of your drives configuration and control software, it's pretty much impossible to say what is wrong in your plant. Talk to your vendor.

Rob Lyon   

answered 17 days ago


 


By Rob Lyon on 9/6/2017 | Like (0) | Report

note : Off1 = LSB = Bit0 etc. Sorry


Add New Comment


0

Hi!

It's not mentioned how your drives are connected to your controller?

Beware if you changed drives from the ACS600/800-series, there are differences in how the status- and/or control words are mapped. Check the ACS880 manuals for more info.

Good luck!

BEAB   

answered 17 days ago


 


Add New Comment



Get weekly AKS updates


Partner Exclusive Webinars

 

> – Login to the partner portal to register



Points Redemption Program - Redeem your points for ABB training, Bluetooth speakers and mugs. Terms and conditions >


Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more



AKS Experts


avatar
Ask nikismith   

Rank: 261

I have been a part of the Recording & Control Factory team for 17 years in total, having spent a number of years as a repairs technician withi the manufacturing department, but being in my current role for 9 years now.


avatar
Ask Flavio Mussolin   

Rank: 5

ABB AVP, Senior Electronic and Automation Engineer with over 30 years of experience in the field of process automation automotive, pharmaceutical, hollow glass, steel and rolling.


avatar
Ask MMM   

Rank: 4

ABB PA CT Technical Support


avatar
Ask Govindaraj   

Rank: 10

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.


avatar
Ask Rob Lyon   

Rank: 3

info@lymac.co.nz I'm an independent DCS software and commissioning engineer with extensive experience in 800xA and other ABB products. I've worked in almost every corner of the world and still haven't seen it all.


avatar
Ask Harsha.D   

Rank: 6

Tech.Support,software and commisioning engineer with Proficient knowledge in 800xA and its products, RNRP,Networking in general.


avatar
Ask Dieter Henkel   

Rank: 24


avatar
Ask Stefan Stromqvist   

Rank: 1

I joined ABB in the year of 1994 and has since 1999 been working as a Service & Support Engineer at BU Control Technologies in Västerås, Sweden. My areas of expertise are: 800xA Base, 800xA for Advant Master, Information Management, operating systems, RNRP and Ethernet comms/networking in general.


avatar
Ask kstoilov   

Rank: 21

Control System Engineer: 800xA, Compact 800, AC500, AC31-50, Advant Master, Simatic, AC&DC Drives 11 years worked for ABB - Control Systems


avatar
Ask Sumit Gargav   

Rank: 2

I have worked with Freelance in majority, with 800xA FD and Melody system partly. Also had opportunity to work with Protocols - HART,Profibus,FF & Modbus.