ABB Power/Ground Testing

Per ABB document, 3BUA000258-510 System 800xA Site Planning System Version 5.1:

“Verification and testing of the AC power distribution system and the grounding system is mandatory at the time of installation and before power is applied to the control system.

After that, the document tells you to contact ABB technical support.
I have an old copy of the testing procedure that was used by the Bailey Controls company. In its day, it was considered an industry standard. Does anyone know if ABB has similar test documentation?.


Add New Comment


JClouseau   

asked 2 years ago
Closed



Answers

2

Please ask your regional ABB support center to assist you.

This topic has become "hot" during recent years when several large projects have run into problems due to, what has later been found improper grounding and installation.

I'm not aware of any test procedure, but the S800 I/O Getting Started (3BSE020923-510) document contain guidelines and requirements. The rules there were developed by our colleague Dr Sten Benda (now retired). For additional information, please read his book: http://www.amazon.com/Interference-free-Electronics-Applications-Sten
-Benda/dp/0862382556

- Only one ground plane is discussed. If site has both "instrument" and "power" ground they must be well isolated from each other. There shall be no voltage difference between them. This is easily measured with a voltmeter.

- Where does the outgoing ground cable end up? Hidden under a rug in the next room, or properly grounded according to professional installation rules?

- Ground cable cross section area minimum is (35mm2 / 2 AVG). Braided ground straps have good characteristics and can be used, e.g. between cabinet and door. Ground currents can be measured with a clamp on ohmmeter.

- All ground connections should be properly made (paint must be removed, self tapping screws often provide better connection, professional clamping tools are preferred over DIY stuff, bolts and nuts should be of proper size and be tightened properly, etc.).

- DIN rails for use with S800 IO need proper support (e.g. mounted on a metal sheet) with self-tapping screws and no washers with a distance not exceeding 100 mm.

- All connections from ground up to the DIN rail should be of "low ohmic" type. The resistance between ground and any later point shall not exceeed 1 ohm. This is easily tested with an ohmmeter.

- Theoretically, there should be no currents in a ground cable. With poor installation (e.g. lack of grounding or grounding made with high resistance joints) ground current could travel in the instrument wires causing a wide range of problems.

Stefan Stromqvist   

answered 2 years ago


 


By JClouseau on 12/9/2015 | Like (0) | Report

Thank you Stefan.


Add New Comment


0

Hi Dave, the only official power and grounding documentation is the Site Planning manual(3BUA000258R5101 for 800Xa) which follows all the codes and standards for installation which is all based on IEEE 1100-2005 which is the current version.  There is also an ABB University course (M301) which goes into all the systems and actually how to perform the testing. There have been several documents written by field service of things to look at  before applying power to the system but I don't recall any of them ever being turned into standards other then the Site Planning manual

jday105   

answered 2 years ago


 


Add New Comment



Get weekly AKS updates


Partner Exclusive Webinars

 

> – Login to the partner portal to register



Points Redemption Program - Redeem your points for ABB training, Bluetooth speakers and mugs. Terms and conditions >


Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more



AKS Experts


avatar
Ask Govindaraj   

Rank: 9

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.


avatar
Ask kstoilov   

Rank: 11

Control System Engineer: 800xA, Compact 800, AC500, AC31-50, Advant Master, Simatic, AC&DC Drives 11 years worked for ABB - Control Systems


avatar
Ask Harsha.D   

Rank: 7

Tech.Support,software and commisioning engineer with Proficient knowledge in 800xA and its products, RNRP,Networking in general.


avatar
Ask Flavio Mussolin   

Rank: 4

ABB AVP, Senior Electronic and Automation Engineer with over 30 years of experience in the field of process automation automotive, pharmaceutical, hollow glass, steel and rolling.


avatar
Ask MMM   

Rank: 5

ABB PA CT Technical Support


avatar
Ask Dieter Henkel   

Rank: 19


avatar
Ask nikismith   

Rank: 255

I have been a part of the Recording & Control Factory team for 17 years in total, having spent a number of years as a repairs technician withi the manufacturing department, but being in my current role for 9 years now.


avatar
Ask WvanWees   

Rank: 6

I'm a senior service engineer working for ABB in The Netherlands.


avatar
Ask Ronny Lindström   

Rank: 16

ABB Service Engineer


avatar
Ask Stefan Stromqvist   

Rank: 1

I joined ABB in the year of 1994 and has since 1999 been working as a Service & Support Engineer at BU Control Technologies in Västerås, Sweden. My areas of expertise are: 800xA Base, 800xA for Advant Master, Information Management, operating systems, RNRP and Ethernet comms/networking in general.


avatar
Ask Sumit Gargav   

Rank: 3

I have worked with Freelance in majority, with 800xA FD and Melody system partly. Also had opportunity to work with Protocols - HART,Profibus,FF & Modbus.


avatar
Ask Rob Lyon   

Rank: 2

info@lymac.co.nz I'm an independent DCS software and commissioning engineer with extensive experience in 800xA and other ABB products. I've worked in almost every corner of the world and still haven't seen it all.