We have one PM865 used for F&G system. We use standard function block in supervisionLib and FireAndGaslib for our project.

For example in Detector2Real function block we need to log Inhibit detector in alarm event list.

but in standard function block we haven't event for inhibit.

if it possible create alarm and event in PPA without change Function block in Control Builder?

because Standard FB is locked.

If you can any solution for my problem please help me.

Thanks


Add New Comment


akokhaledi   

asked 2 months ago
Closed



Best Answer

1

Yes, but I sincerely recommend creating the event from a SimpleEventDetector or AlarmCond block in the controller. You need to find the trigger signal though.

A SoftAlarm (Alarm Expression) could give a similar apperance, but to the price of additional OPC communcation. Plus, SoftAlarms are a magnitude less (or worse) reliable than a real event or alarm collected via OPC AE from an OPC server.

Stefan Stromqvist   

answered 2 months ago


 


By akokhaledi on 8/10/2017 | Like (0) | Report

Please explain to me Why SoftAlarm is less reliable according to OPC AE from Coltroller?
We have very much detector in our project. and if we use AlarmCondM and SimpleEventDetector this is very difficult and want very much time.
if we use alarm expression in object type structure its very easy. But I need to know that use Alarm Expression have What is the risk?


By Stefan Stromqvist on 8/10/2017 | Like (0) | Report

1. Alarm Expressions are excuted "far away" from the controller. A communication problem, etc. may prevent expressions to fire.

2. There is a 1-2 second delay in expressions due to latency in MMS and OPC layers.

3. Alarm expressions add to the OPC burden and MMS load on the controller. Data feed need to run 24x365.

4. Alarm expressions have other drawbacks making it a lesser attractive alternative than controller generated alarms (Microsoft Windows is "just" Windows not the best realtime server operating system to depend upon, hotfixes, anti-virus, networking makes whole equation much more complex, etc)

5. The maximum capacity of SoftAlarm service is difficult to fathom; overload may cause a collapse in all expressions.


By akokhaledi on 8/10/2017 | Like (0) | Report

Ok
Consequencly you think we should be use alarmcondm and simpleevent control module that loaded in controller.
But are you have any solution for repeat for all of detector. (We want log inhibit).
One simple way without show in control module. Because now my cotrol module is very busy.


By Stefan Stromqvist on 8/10/2017 | Like (0) | Report

No idea, maybe the hint from insades1 is possible?


Add New Comment


Answers

1

Yes, but I sincerely recommend creating the event from a SimpleEventDetector or AlarmCond block in the controller. You need to find the trigger signal though.

A SoftAlarm (Alarm Expression) could give a similar apperance, but to the price of additional OPC communcation. Plus, SoftAlarms are a magnitude less (or worse) reliable than a real event or alarm collected via OPC AE from an OPC server.

Stefan Stromqvist   

answered 2 months ago


 


By akokhaledi on 8/10/2017 | Like (0) | Report

Please explain to me Why SoftAlarm is less reliable according to OPC AE from Coltroller?
We have very much detector in our project. and if we use AlarmCondM and SimpleEventDetector this is very difficult and want very much time.
if we use alarm expression in object type structure its very easy. But I need to know that use Alarm Expression have What is the risk?


By Stefan Stromqvist on 8/10/2017 | Like (0) | Report

1. Alarm Expressions are excuted "far away" from the controller. A communication problem, etc. may prevent expressions to fire.

2. There is a 1-2 second delay in expressions due to latency in MMS and OPC layers.

3. Alarm expressions add to the OPC burden and MMS load on the controller. Data feed need to run 24x365.

4. Alarm expressions have other drawbacks making it a lesser attractive alternative than controller generated alarms (Microsoft Windows is "just" Windows not the best realtime server operating system to depend upon, hotfixes, anti-virus, networking makes whole equation much more complex, etc)

5. The maximum capacity of SoftAlarm service is difficult to fathom; overload may cause a collapse in all expressions.


By akokhaledi on 8/10/2017 | Like (0) | Report

Ok
Consequencly you think we should be use alarmcondm and simpleevent control module that loaded in controller.
But are you have any solution for repeat for all of detector. (We want log inhibit).
One simple way without show in control module. Because now my cotrol module is very busy.


By Stefan Stromqvist on 8/10/2017 | Like (0) | Report

No idea, maybe the hint from insades1 is possible?


Add New Comment


1

To create an Alarm or Event out of Detector2Real block now as you you do not want to change/Wrap original block, I would suggest to create a Alarm Block in Library and connect GTHActInh/GTHHActInh or AreaInhibited to Alarm Block to Generate Alarm/Event further. You can add Name/Description Paramter to Alarm Block to get project Alarm List presentation.

insades1   

answered 2 months ago


 


Add New Comment



Get weekly AKS updates


Partner Exclusive Webinars

 

> – Login to the partner portal to register



Points Redemption Program - Redeem your points for ABB training, Bluetooth speakers and mugs. Terms and conditions >


Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more



AKS Experts


avatar
Ask Govindaraj   

Rank: 10

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.


avatar
Ask Dieter Henkel   

Rank: 23


avatar
Ask MMM   

Rank: 4

ABB PA CT Technical Support


avatar
Ask kstoilov   

Rank: 17

Control System Engineer: 800xA, Compact 800, AC500, AC31-50, Advant Master, Simatic, AC&DC Drives 11 years worked for ABB - Control Systems


avatar
Ask Harsha.D   

Rank: 6

Tech.Support,software and commisioning engineer with Proficient knowledge in 800xA and its products, RNRP,Networking in general.


avatar
Ask nikismith   

Rank: 261

I have been a part of the Recording & Control Factory team for 17 years in total, having spent a number of years as a repairs technician withi the manufacturing department, but being in my current role for 9 years now.


avatar
Ask Sumit Gargav   

Rank: 2

I have worked with Freelance in majority, with 800xA FD and Melody system partly. Also had opportunity to work with Protocols - HART,Profibus,FF & Modbus.


avatar
Ask Flavio Mussolin   

Rank: 5

ABB AVP, Senior Electronic and Automation Engineer with over 30 years of experience in the field of process automation automotive, pharmaceutical, hollow glass, steel and rolling.


avatar
Ask Rob Lyon   

Rank: 3

info@lymac.co.nz I'm an independent DCS software and commissioning engineer with extensive experience in 800xA and other ABB products. I've worked in almost every corner of the world and still haven't seen it all.


avatar
Ask Stefan Stromqvist   

Rank: 1

I joined ABB in the year of 1994 and has since 1999 been working as a Service & Support Engineer at BU Control Technologies in Västerås, Sweden. My areas of expertise are: 800xA Base, 800xA for Advant Master, Information Management, operating systems, RNRP and Ethernet comms/networking in general.