800xA 5.1 Rev E with AC450 - Redundancy Problem

Dear all




A custumer told about problem in system redundancy. The problem is occurring when the system lost the redundancy ( CS primary or secondary). If we lost only PU410 didn’t happing anything.




1° test: Turn Of PU410 redundat and the system switch the services (MB300) perfectly.


2° test: The same test n°1 but turn off Pu410 Primary. Switch the services perfectly.


3° test: Turn off secundary CS server and the switch take more then 2 minutes and occurs lost OPC. In the same MB300 has AS500 and lose to dynamic reference too.



4° test: The same test n°3 but torn off primary CS server and the problem was the same.



When Turnf Off the Cs server was happeing something in MB300.


I don't Know yet if this problem is a " MB300 BackPressure". Next week I will take more details like:


FTCCB ,,, in RTA bord


Log in RTA manager tool



Is it possible a incompatibility between the 800xA and AS500 system? The Costumer didn't do the test removing AS500.


attachment MB300 Switch (both are the same status) configurations. In the Principal and Secondary Switch CRC error are more then 5% (recommended).



Thanks.


 MB300 Switch Princip.jpeg

 MB300 Switch Princip.jpeg


Add New Comment


Bruno.S   

asked 3 months ago
Closed



Answers

0

RTA System Messages?

- Before/during test #3 and #4, please login to the server that is to be kept up and running and check if any System Messages are output in the RTA Board Configuration tool (remember to verify that message output to screen is enabled, or else they will only be saved to the log). Report messages with full detail.

What is the revision of the controllers?

- versions older than AC450 2.3/5 may stop sending data to ALL RTAs during backpressure.

What is the subscription load?

- with high amount of subscriptions running, a failover could be a very stressful event.

What is the RTA CPU load?

- for smooth failover, RTA CPU load should be kept below 50%, preferably below 40%.

Remember: The PU410 connection with the host computer is hardcoded to 100 mbit full duplex at PU410 side. Some NICs don’t handle a fixed speed setting so well. Attempting to auto-negotiate from host side could result in host NIC selecting 100 *half* duplex. At higher throughputs, a mismatch in duplex could lead to major losses. Verify the PU410 and host communication. Potentially interposition a managed switch to be able to monitor port error counters (at full duplex, expect more or less zero errors).

Stefan Stromqvist   

answered 3 months ago


 


Add New Comment


0

Both CS should be live at the same time. So the fact that you get bad OPC data implies that your 800xA clients are "stuck" on the stopped CS and have not failed over to the backup CS properly. When they do finally failover, everything works OK. This sounds like an "800xA" problem - not an AC450 / Masterbus problem.

A 2 minute delay implies RNRP isnt working properly and the clients are waiting for a base TCP/IP timeout before realizing the server is unavailable.

- Check the RNRP configuration for each CS. Ensure that Both the Plant Networks are configured correctly and that your Plant Networks and Control Networks are on separate areas. Note that the MB300 areas (ie the connection between the CS and the RTA) are local to the PC and should be local RNRP networks.

- Check Server affinity and load sharing settings. Check to see if all of the clients are attached to CS1 at the same time or spread over both CS1 and CS2.

- You described that you stop the RTA on CS2 first, which forces clients to use CS1, then stop CS1 whch forces all the clients back to CS2. What happens when you do this test in "reverse order" - i.e. After a long period of stable running, you begin with the RTA on CS1

Rob Lyon   

answered 3 months ago


 


Add New Comment



Get weekly AKS updates


Partner Exclusive Webinars

 

> – Login to the partner portal to register



Points Redemption Program - Redeem your points for ABB training, Bluetooth speakers and mugs. Terms and conditions >


Earn points when you refer a friend
AKS Referral Program is "Live" - Learn more



AKS Experts


avatar
Ask MMM   

Rank: 5

ABB PA CT Technical Support


avatar
Ask Govindaraj   

Rank: 10

Working in ABB India Operation Center. Have Project engineering and commissioning experience in ABB 800xA, Freelance, AC500.


avatar
Ask Flavio Mussolin   

Rank: 4

ABB AVP, Senior Electronic and Automation Engineer with over 30 years of experience in the field of process automation automotive, pharmaceutical, hollow glass, steel and rolling.


avatar
Ask Sumit Gargav   

Rank: 3

I have worked with Freelance in majority, with 800xA FD and Melody system partly. Also had opportunity to work with Protocols - HART,Profibus,FF & Modbus.


avatar
Ask kstoilov   

Rank: 9

Control System Engineer: 800xA, Compact 800, AC500, AC31-50, Advant Master, Simatic, AC&DC Drives 11 years worked for ABB - Control Systems


avatar
Ask Harsha.D   

Rank: 7

Tech.Support,software and commisioning engineer with Proficient knowledge in 800xA and its products, RNRP,Networking in general.


avatar
Ask WvanWees   

Rank: 6

I'm a senior service engineer working for ABB in The Netherlands.


avatar
Ask Stefan Stromqvist   

Rank: 1

I joined ABB in the year of 1994 and has since 1999 been working as a Service & Support Engineer at BU Control Technologies in Västerås, Sweden. My areas of expertise are: 800xA Base, 800xA for Advant Master, Information Management, operating systems, RNRP and Ethernet comms/networking in general.


avatar
Ask Rob Lyon   

Rank: 2

info@lymac.co.nz I'm an independent DCS software and commissioning engineer with extensive experience in 800xA and other ABB products. I've worked in almost every corner of the world and still haven't seen it all.


avatar
Ask nikismith   

Rank: 257

I have been a part of the Recording & Control Factory team for 17 years in total, having spent a number of years as a repairs technician withi the manufacturing department, but being in my current role for 9 years now.


avatar
Ask Dieter Henkel   

Rank: 19


avatar
Ask Ronny Lindström   

Rank: 17

ABB Service Engineer